Menu

Heating and Air Conditioning Services in Anna, TX

Adon Complete Air Conditioning and Heating is Anna’s local HVAC company. Most contractors serving this area are driving in from McKinney or further south. We’re not. Our office is right here in Anna. Our owner, Jesse Villarreal, has been serving Collin County homeowners for over 27 years, and our technicians run calls in Anna neighborhoods every single day. Whether you’re in an established neighborhood near downtown, a newer community like Liberty Hills, or getting ready to move into Sherley Farms, we know this city and we’re ready to help.

Schedule Service in AnnaCall (903) 482-4900

HVAC Services in Anna, TX

Anna is one of the fastest-growing cities in North Texas, and with thousands of new homes coming online, the demand for reliable heating and cooling service has never been higher. Here’s what we offer Anna homeowners:

AC Repair. Fast diagnosis and repair on all makes and models. We’re already in Anna every day, which means getting to you quickly isn’t a problem.

AC Installation. Whether you’re moving into a new build or replacing an aging system, we size every installation correctly using a proper load calculation. All new installations come with up to a 10-year labor warranty.

HVAC Maintenance. Our Adon Care Club is $12 a month and includes two seasonal tune-ups, priority scheduling, repair discounts, and 24/7 emergency access. For Anna homeowners in new construction, getting on a maintenance plan early is one of the best ways to protect your warranty and catch issues before they become expensive.

Mini-Split Installation. Ductless systems work especially well for garages, home offices, bonus rooms, and additions, all of which are common in Anna’s newer construction neighborhoods.

Heat Pump Installation and Repair. Heat pumps provide year-round heating and cooling from one system. A popular option for Anna’s newer builds where energy efficiency matters.

Indoor Air Quality. New construction homes are built tight for energy efficiency, which means less fresh air circulation. Air filtration systems, UV purifiers, and ventilators help keep the air inside your home clean and healthy. We offer a free “What Are You Breathing?” screening to Anna homeowners.

Air Duct Cleaning. Construction dust and debris in ductwork is a real issue in new builds. Professional duct cleaning after move-in is something we recommend for most Anna homeowners in newer communities.

Air Duct Repair and Sealing. Leaky ducts can cost you 20 to 30 percent of your system’s output. We inspect, repair, and seal ductwork throughout Anna and Collin County.

HVAC Services for Anna’s Growing Neighborhoods

Anna’s population grew roughly 177 percent between 2022 and 2023, making it one of the fastest-growing cities in the country. Sherley Farms, a $1.5 billion master-planned community, broke ground in March 2026 and will bring roughly 3,000 new homes to the city over the next several years. Liberty Hills is adding another 1,800 homes near US-75. That’s thousands of new HVAC systems coming online in a city that’s already one of our busiest service areas.

For homeowners in newer construction, the first few years matter most. Builder-installed systems need to be maintained on schedule to keep warranties valid, and new ductwork should be inspected and cleaned after construction is complete. We’ve helped Anna homeowners navigate all of this, and we know exactly what to look for.

Why Anna Homeowners Choose Adon Complete

Schedule Service in AnnaCall (903) 482-4900

Frequently Asked Questions

Here are some answers to common questions we get about our Anna HVAC services.

How much does AC repair cost in Anna, TX?

Most AC repairs in Anna run between $150 and $600, depending on the type of repair. Simple fixes like a capacitor replacement are on the lower end. More involved repairs, like a blower motor or evaporator coil, will cost more. We provide a clear estimate before any work begins. Call (903) 482-4900 to schedule a diagnostic visit.

Do you offer emergency HVAC service in Anna?

Yes. We offer 24/7 emergency heating and air conditioning service throughout Anna and Collin County. Since we’re based in Anna, response times are typically faster here than anywhere else we serve.

What HVAC brands do you service in Anna?

We service all makes and models, including Trane, Lennox, Carrier, Daikin, Mitsubishi, Goodman, Rheem, and more. As a Trane Comfort Specialist and Mitsubishi-authorized dealer, we have factory-trained expertise in those brands.

Do you offer HVAC maintenance plans in Anna?

Yes. Our Adon Care Club is $12 a month and includes two seasonal tune-ups, priority scheduling, repair discounts, no diagnostic fees, and 24/7 emergency response. For new construction homeowners especially, staying on a maintenance schedule helps protect your builder warranty.

What areas near Anna do you serve?

We serve all of Anna and the surrounding Collin County communities, including McKinney, Sherman, Melissa, Van Alstyne, and Allen.

Schedule HVAC Service in Anna Today

We’re already in your neighborhood. Call Adon Complete Air Conditioning and Heating at (903) 482-4900 or schedule online.

Schedule Service in AnnaCall (903) 482-4900

Recent Jobs and Reviews in Anna, TX

Rated 4.9 out of 5 stars based on 67 customer reviews

Customers say: The overall sentiment across these reviews is overwhelmingly positive, reflecting strong customer satisfaction and appreciation for the service provided. Customers consistently praise the professionalism, knowledge, and efficiency of the technicians, highlighting their courteous demeanor and thorough explanations of work performed. A recurring theme is the company's responsiveness, with many reviewers expressing gratitude for quick arrival times, same-day or next-day service, and emergency availability during hot weather conditions. The honest, straightforward approach without upselling or gimmicks is frequently mentioned as a standout quality that builds trust. Customers appreciate the clear communication from both technicians and office staff, including timely updates on arrival times. The friendly and patient attitudes of service providers, even in stressful situations, earn particular commendation. Many reviewers indicate they would highly recommend the company and plan to use their services again, with several noting this is their preferred choice after multiple positive experiences. The tone is enthusiastic and grateful, with customers feeling valued and well-served, particularly during urgent situations involving AC failures in extreme heat. Overall, the reviews convey a strong sense of reliability, integrity, and customer-focused service that generates loyalty and satisfaction.

Anna, TX at a glance

Adon Complete Air Conditioning and Heating has completed 10 jobs in Anna, TX in May 2026.

The most recent job was on May 18, 2026.

Adon Complete Air Conditioning and Heating has completed 588 jobs in Anna, TX in the last 12 months. The first job there was in February 2020.

Job Locations

Matthew C.
Matthew C.
Upon arrival client stated the downstairs unit wasnt running but the fan was blowing. I checked the outside unit. The condenser fan was running but not the compressor. After a series of test on the compressor. I found that the compressor was locked up and not pumping refrigerant levels are good.
Anna, TX 75409
Anna, TX - Upon arrival client stated the downstairs unit wasnt running but the fan was blowing. I checked the outside unit. The condenser fan was running but not the compressor. After a series of test on the compressor. I found that the compressor was locked up and not pumping refrigerant levels are good.
Anna, TX - Upon arrival client stated the downstairs unit wasnt running but the fan was blowing. I checked the outside unit. The condenser fan was running but not the compressor. After a series of test on the compressor. I found that the compressor was locked up and not pumping refrigerant levels are good.
Matthew C.
Matthew C.
Changed filter for client 20x25x4
Anna, TX 75409
Anna, TX - Changed filter for client 20x25x4
Anna, TX - Changed filter for client 20x25x4
Matthew C.
Matthew C.
Cleared drain line Vacuuming out water in drain pan. Clearing the drain line CLEAR DRAIN BLOCK - USING NITROGEN ONLY LEVEL 3 CONDENSATE DRAIN LINES NEED TO BE CLEANED OR THEY CAN CLOG WITH ALGAE AND DEBRIS Includes shop vacuuming when necessary and 1 PVC Coupling Also installation of a Quickblast PVC fitting, SS1 Safety Switch, P-Trap, and Vent Pipe.
Anna, TX 75409
Anna, TX - Cleared drain line 

Vacuuming out water in drain pan.
Clearing the drain line 

CLEAR DRAIN BLOCK - USING NITROGEN ONLY LEVEL 3

CONDENSATE DRAIN LINES NEED TO BE CLEANED OR THEY CAN CLOG WITH ALGAE AND DEBRIS

Includes shop vacuuming when necessary and 1 PVC Coupling

Also installation of a Quickblast PVC fitting, SS1 Safety Switch, P-Trap, and Vent Pipe.
Anna, TX - Cleared drain line 

Vacuuming out water in drain pan.
Clearing the drain line 

CLEAR DRAIN BLOCK - USING NITROGEN ONLY LEVEL 3

CONDENSATE DRAIN LINES NEED TO BE CLEANED OR THEY CAN CLOG WITH ALGAE AND DEBRIS

Includes shop vacuuming when necessary and 1 PVC Coupling

Also installation of a Quickblast PVC fitting, SS1 Safety Switch, P-Trap, and Vent Pipe.
Brayden W.
Brayden W.
Found outdoor fan motor not running while compressor would run in cooling call. Tested outdoor electrical and found capacitor and contactor testing within range. Hard start kit was failed. Checked wiring schematic and found purple and black wire to the motor was flipped. Switched wires to line up with wiring diagram and tested unit. Unit came on without issue and began cooling. Temperature split is low 15 degrees. Advised homeowner that this is likely due to dirty coils on a system this old. However it is not recommended to clean these coils due to rust and age increasing the likelyhood of cleaning causing a leak. Provided estimates for maintenance program and new hard start kit. System running upon departure.
Anna, TX 75409
Anna, TX - Found outdoor fan motor not running while compressor would run in cooling call. Tested outdoor electrical and found capacitor and contactor testing within range. Hard start kit was failed. Checked wiring schematic and found purple and black wire to the motor was flipped. Switched wires to line up with wiring diagram and tested unit. Unit came on without issue and began cooling. Temperature split is low 15 degrees. Advised homeowner that this is likely due to dirty coils on a system this old. However it is not recommended to clean these coils due to rust and age increasing the likelyhood of cleaning causing a leak. Provided estimates for maintenance program and new hard start kit. System running upon departure.
Anna, TX - Found outdoor fan motor not running while compressor would run in cooling call. Tested outdoor electrical and found capacitor and contactor testing within range. Hard start kit was failed. Checked wiring schematic and found purple and black wire to the motor was flipped. Switched wires to line up with wiring diagram and tested unit. Unit came on without issue and began cooling. Temperature split is low 15 degrees. Advised homeowner that this is likely due to dirty coils on a system this old. However it is not recommended to clean these coils due to rust and age increasing the likelyhood of cleaning causing a leak. Provided estimates for maintenance program and new hard start kit. System running upon departure.
Brayden W.
Brayden W.
1. Visually inspected condenser coil for leaks and abnormalities. 2. Inspected condenser fan motor, blades and bearings. 3. Inspected, cleaned, and, tightened wiring connections. 4. Measured capacitance of compressor/fan motor capacitor. 5. Inspected and measured resistance of contactor 6. Measured compressor current draw. 7. Measured condenser fan motor amp draw. 8. Inspected and replaced return filter. 9. Inspected return plenum for dust or debris. 10. Inspected evaporator coil for cleanliness and oxidation. 11. Inspected blower motor/ blower wheel for dust and debris 12. Measured blower motor current draw. 13. Measured temperature differential from supply to return. 20 degrees measured. 14. Tested drain lines for proper drainage and treated to prevent blockages. 15. Rinsed condenser with water to promote heat exchange and reduce stress on system by removing dust and debris. Replaced bad capacitor under parts and labor warranty. Found outside condenser coils to be dirty even aft
Anna, TX 75409
Anna, TX - 1.  Visually inspected condenser coil for leaks and abnormalities.
2. Inspected condenser fan motor, blades and bearings.
3. Inspected, cleaned, and, tightened wiring connections.
4. Measured capacitance of  compressor/fan motor capacitor.
5. Inspected and measured resistance of contactor
6. Measured compressor current draw.
7. Measured condenser fan motor amp draw.
8. Inspected and replaced return filter.
9. Inspected return plenum for dust or debris.
10. Inspected evaporator coil for cleanliness and oxidation.
11. Inspected blower motor/ blower wheel for dust and debris
12. Measured blower motor current draw.
13. Measured temperature differential from supply to return. 20 degrees measured.
14. Tested drain lines for proper drainage and treated to prevent blockages.
15. Rinsed condenser with water to promote heat exchange and reduce stress on system by removing dust and debris.

Replaced bad capacitor under parts and labor warranty. 

Found outside condenser coils to be dirty even aft
Anna, TX - 1.  Visually inspected condenser coil for leaks and abnormalities.
2. Inspected condenser fan motor, blades and bearings.
3. Inspected, cleaned, and, tightened wiring connections.
4. Measured capacitance of  compressor/fan motor capacitor.
5. Inspected and measured resistance of contactor
6. Measured compressor current draw.
7. Measured condenser fan motor amp draw.
8. Inspected and replaced return filter.
9. Inspected return plenum for dust or debris.
10. Inspected evaporator coil for cleanliness and oxidation.
11. Inspected blower motor/ blower wheel for dust and debris
12. Measured blower motor current draw.
13. Measured temperature differential from supply to return. 20 degrees measured.
14. Tested drain lines for proper drainage and treated to prevent blockages.
15. Rinsed condenser with water to promote heat exchange and reduce stress on system by removing dust and debris.

Replaced bad capacitor under parts and labor warranty. 

Found outside condenser coils to be dirty even aft
Matthew C.
Matthew C.
Completed single system maintenance on a 2021 goodman. Gas. I tested all electrical components on the inside unit. All tested within manufacturer specifications. The system is cooling mostly in manufacture specifications. The compressor is over amping on start up. This leads to internal damage over years resulting in the compressor failing. The ducts are poorly designed. This is causing poor airflow to the master portion of the house and a whistling noise coming from one of the return. The duct to the master area is a 9” that feeds 2 - 7” ducts. We need to upsize the duct to a 12”. This would allow us to supply the 7s with appropriate air flow. The systems are designed to have so much return air. The system currently does not have enough. This causes high static pressure and it is one of the leading causes of system failure. High static pressure strains all of the major parts of an air conditioner. Unit is cooling upon departure.
Anna, TX 75409
Anna, TX - Completed single system maintenance on a 2021 goodman. Gas. I tested all electrical components on the inside unit. All tested within manufacturer specifications. The system is cooling mostly in manufacture specifications. The compressor is over amping on start up. This leads to internal damage over years resulting in the compressor failing. The ducts are poorly designed. This is causing poor airflow to the master portion of the house and a whistling noise coming from one of the return. The duct to the master area is a 9” that feeds 2 - 7” ducts. We need to upsize the duct to a 12”. This would allow us to supply the 7s with appropriate air flow. The systems are designed to have so much return air. The system currently does not have enough. This causes high static pressure and it is one of the leading causes of system failure. High static pressure strains all of the major parts of an air conditioner. Unit is cooling upon departure.
Anna, TX - Completed single system maintenance on a 2021 goodman. Gas. I tested all electrical components on the inside unit. All tested within manufacturer specifications. The system is cooling mostly in manufacture specifications. The compressor is over amping on start up. This leads to internal damage over years resulting in the compressor failing. The ducts are poorly designed. This is causing poor airflow to the master portion of the house and a whistling noise coming from one of the return. The duct to the master area is a 9” that feeds 2 - 7” ducts. We need to upsize the duct to a 12”. This would allow us to supply the 7s with appropriate air flow. The systems are designed to have so much return air. The system currently does not have enough. This causes high static pressure and it is one of the leading causes of system failure. High static pressure strains all of the major parts of an air conditioner. Unit is cooling upon departure.
Brayden W.
Brayden W.
1. Visually inspected condenser coil for leaks and abnormalities. 2. Inspected condenser fan motor, blades and bearings. 3. Inspected, cleaned, and, tightened wiring connections. 4. Measured capacitance of compressor/fan motor capacitor. 5. Inspected and measured resistance of contactor 6. Measured compressor current draw. 7. Measured condenser fan motor amp draw. 8. Inspected and replaced return filter. 9. Inspected return plenum for dust or debris. 10. Inspected evaporator coil for cleanliness and oxidation. 11. Inspected blower motor/ blower wheel for dust and debris 12. Measured blower motor current draw. 13. Measured temperature differential from supply to return. 20 degrees measured. 14. Tested drain lines for proper drainage and treated to prevent blockages. 15. Rinsed condenser with water to promote heat exchange and reduce stress on system by removing dust and debris. Refrigerant pressure were measuring within manufacturer specs for the most part superheat was a bit high. N
Anna, TX 75409
Anna, TX - 1.  Visually inspected condenser coil for leaks and abnormalities.
2. Inspected condenser fan motor, blades and bearings.
3. Inspected, cleaned, and, tightened wiring connections.
4. Measured capacitance of  compressor/fan motor capacitor.
5. Inspected and measured resistance of contactor
6. Measured compressor current draw.
7. Measured condenser fan motor amp draw.
8. Inspected and replaced return filter.
9. Inspected return plenum for dust or debris.
10. Inspected evaporator coil for cleanliness and oxidation.
11. Inspected blower motor/ blower wheel for dust and debris
12. Measured blower motor current draw.
13. Measured temperature differential from supply to return. 20 degrees measured.
14. Tested drain lines for proper drainage and treated to prevent blockages.
15. Rinsed condenser with water to promote heat exchange and reduce stress on system by removing dust and debris.

Refrigerant pressure were measuring within manufacturer specs for the most part superheat was a bit high. N
Anna, TX - 1.  Visually inspected condenser coil for leaks and abnormalities.
2. Inspected condenser fan motor, blades and bearings.
3. Inspected, cleaned, and, tightened wiring connections.
4. Measured capacitance of  compressor/fan motor capacitor.
5. Inspected and measured resistance of contactor
6. Measured compressor current draw.
7. Measured condenser fan motor amp draw.
8. Inspected and replaced return filter.
9. Inspected return plenum for dust or debris.
10. Inspected evaporator coil for cleanliness and oxidation.
11. Inspected blower motor/ blower wheel for dust and debris
12. Measured blower motor current draw.
13. Measured temperature differential from supply to return. 20 degrees measured.
14. Tested drain lines for proper drainage and treated to prevent blockages.
15. Rinsed condenser with water to promote heat exchange and reduce stress on system by removing dust and debris.

Refrigerant pressure were measuring within manufacturer specs for the most part superheat was a bit high. N
Brayden W.
Brayden W.
1. Visually inspected condenser coil for leaks and abnormalities. 2. Inspected condenser fan motor, blades and bearings. 3. Inspected, cleaned, and, tightened wiring connections. 4. Measured capacitance of compressor/fan motor capacitor. 5. Inspected and measured resistance of contactor 6. Measured compressor current draw. 7. Measured condenser fan motor amp draw. 8. Inspected and replaced return filter. 9. Inspected return plenum for dust or debris. 10. Inspected evaporator coil for cleanliness and oxidation. 11. Inspected blower motor/ blower wheel for dust and debris 12. Measured blower motor current draw. 13. Measured temperature differential from supply to return. 20 degrees measured. 14. Tested drain lines for proper drainage and treated to prevent blockages. 15. Rinsed condenser with water to promote heat exchange and reduce stress on system by removing dust and debris. Found high start amps on outdoor condenser. High start amps indicates that the unit is struggling to start
Anna, TX 75409
Anna, TX - 1.  Visually inspected condenser coil for leaks and abnormalities.
2. Inspected condenser fan motor, blades and bearings.
3. Inspected, cleaned, and, tightened wiring connections.
4. Measured capacitance of  compressor/fan motor capacitor.
5. Inspected and measured resistance of contactor
6. Measured compressor current draw.
7. Measured condenser fan motor amp draw.
8. Inspected and replaced return filter.
9. Inspected return plenum for dust or debris.
10. Inspected evaporator coil for cleanliness and oxidation.
11. Inspected blower motor/ blower wheel for dust and debris
12. Measured blower motor current draw.
13. Measured temperature differential from supply to return. 20 degrees measured.
14. Tested drain lines for proper drainage and treated to prevent blockages.
15. Rinsed condenser with water to promote heat exchange and reduce stress on system by removing dust and debris.

Found high start amps on outdoor condenser. High start amps indicates that the unit is struggling to start
Anna, TX - 1.  Visually inspected condenser coil for leaks and abnormalities.
2. Inspected condenser fan motor, blades and bearings.
3. Inspected, cleaned, and, tightened wiring connections.
4. Measured capacitance of  compressor/fan motor capacitor.
5. Inspected and measured resistance of contactor
6. Measured compressor current draw.
7. Measured condenser fan motor amp draw.
8. Inspected and replaced return filter.
9. Inspected return plenum for dust or debris.
10. Inspected evaporator coil for cleanliness and oxidation.
11. Inspected blower motor/ blower wheel for dust and debris
12. Measured blower motor current draw.
13. Measured temperature differential from supply to return. 20 degrees measured.
14. Tested drain lines for proper drainage and treated to prevent blockages.
15. Rinsed condenser with water to promote heat exchange and reduce stress on system by removing dust and debris.

Found high start amps on outdoor condenser. High start amps indicates that the unit is struggling to start
Shelby S.
Shelby S.
I performed a single cooling maintenance on a 2020 heat pump system. I checked amps, capacitors, filter, electrical, cleanliness, and drains. During my thorough evaluation, I discovered a substantial amount of growth inside of the air handler and that the equipment did not have surge protection. I presented an options to clean the growth out, install a preventative for the growth, and a surge protector for the outdoor unit.
Anna, TX 75409
Anna, TX - I performed a single cooling maintenance on a 2020 heat pump system. I checked amps, capacitors, filter, electrical, cleanliness, and drains. During my thorough evaluation, I discovered a substantial amount of growth inside of the air handler and that the equipment did not have surge protection. I presented an options to clean the growth out, install a preventative for the growth, and a surge protector for the outdoor unit.
Anna, TX - I performed a single cooling maintenance on a 2020 heat pump system. I checked amps, capacitors, filter, electrical, cleanliness, and drains. During my thorough evaluation, I discovered a substantial amount of growth inside of the air handler and that the equipment did not have surge protection. I presented an options to clean the growth out, install a preventative for the growth, and a surge protector for the outdoor unit.
Brayden W.
Brayden W.
1. Visually inspected condenser coil for leaks and abnormalities. 2. Inspected condenser fan motor, blades and bearings. 3. Inspected, cleaned, and, tightened wiring connections. 4. Measured capacitance of compressor/fan motor capacitor. 5. Inspected and measured resistance of contactor 6. Measured compressor current draw. 7. Measured condenser fan motor amp draw. 8. Inspected and replaced return filter. 9. Inspected return plenum for dust or debris. 10. Inspected evaporator coil for cleanliness and oxidation. 11. Inspected blower motor/ blower wheel for dust and debris 12. Measured blower motor current draw. 13. Measured temperature differential from supply to return. 20 degrees measured. 14. Tested drain lines for proper drainage and treated to prevent blockages. 15. Rinsed condenser with water to promote heat exchange and reduce stress on system by removing dust and debris. Large amount of dust and debris on indoor and outdoor coils. This causes a stress on refrigerant cycle and
Anna, TX 75409
Anna, TX - 1.  Visually inspected condenser coil for leaks and abnormalities.
2. Inspected condenser fan motor, blades and bearings.
3. Inspected, cleaned, and, tightened wiring connections.
4. Measured capacitance of  compressor/fan motor capacitor.
5. Inspected and measured resistance of contactor
6. Measured compressor current draw.
7. Measured condenser fan motor amp draw.
8. Inspected and replaced return filter.
9. Inspected return plenum for dust or debris.
10. Inspected evaporator coil for cleanliness and oxidation.
11. Inspected blower motor/ blower wheel for dust and debris
12. Measured blower motor current draw.
13. Measured temperature differential from supply to return. 20 degrees measured.
14. Tested drain lines for proper drainage and treated to prevent blockages.
15. Rinsed condenser with water to promote heat exchange and reduce stress on system by removing dust and debris.

Large amount of dust and debris on indoor and outdoor coils. This causes a stress on refrigerant cycle and
Anna, TX - 1.  Visually inspected condenser coil for leaks and abnormalities.
2. Inspected condenser fan motor, blades and bearings.
3. Inspected, cleaned, and, tightened wiring connections.
4. Measured capacitance of  compressor/fan motor capacitor.
5. Inspected and measured resistance of contactor
6. Measured compressor current draw.
7. Measured condenser fan motor amp draw.
8. Inspected and replaced return filter.
9. Inspected return plenum for dust or debris.
10. Inspected evaporator coil for cleanliness and oxidation.
11. Inspected blower motor/ blower wheel for dust and debris
12. Measured blower motor current draw.
13. Measured temperature differential from supply to return. 20 degrees measured.
14. Tested drain lines for proper drainage and treated to prevent blockages.
15. Rinsed condenser with water to promote heat exchange and reduce stress on system by removing dust and debris.

Large amount of dust and debris on indoor and outdoor coils. This causes a stress on refrigerant cycle and