HVAC Service in Frisco, TX

Frisco has grown faster than almost any city in America over the past two decades, and the homes here reflect it. Larger floor plans, multi-zone systems, high-efficiency equipment, and newer construction in neighborhoods like The Fields, Phillips Creek Ranch, and Viridian. Keeping all of it running well takes an HVAC company that knows what it’s doing. Adon Complete Air Conditioning and Heating has been running calls for HVAC service in Frisco for years from our home base in Anna, just up the Dallas North Tollway corridor. We’re a Trane Comfort Specialist and Mitsubishi-authorized dealer, and we’re available 24 hours a day, 7 days a week for emergencies.

Schedule HVAC Service in FriscoCall (903) 482-4900

What We Do for Frisco Homeowners

AC Repair. We diagnose and repair all makes and models. Frisco’s newer construction often means multi-zone systems and communicating equipment — our technicians know how to work on all of it.

AC Installation. When it’s time to replace, we size every system correctly using a proper load calculation. That matters especially in Frisco’s larger homes where an improperly sized system will short-cycle and leave rooms uncomfortable. All new installations come with up to a 10-year labor warranty.

HVAC Maintenance. Our Adon Care Club is $12 a month and includes two seasonal tune-ups, priority scheduling, repair discounts, and 24/7 emergency access. For Frisco homeowners with high-end systems, staying on a maintenance schedule is one of the best ways to protect your investment.

Mini-Split Installation. Garages, home offices, casitas, and bonus spaces are common in Frisco’s larger homes. Mini-splits handle these spaces cleanly without touching your central system.

Heat Pump Installation and Repair. Heat pumps provide both heating and cooling from one system and work well in North Texas’s climate. A practical choice for Frisco homeowners upgrading to a more efficient setup.

Indoor Air Quality. Air filtration systems, UV purifiers, humidifiers, dehumidifiers, and a free “What Are You Breathing?” screening. Frisco’s tight construction means less natural ventilation, making air quality systems more important than in older homes.

Air Duct Cleaning. Even newer ductwork accumulates contaminants over time. Professional duct cleaning improves air quality and keeps your system running efficiently throughout the home.

Air Duct Repair and Sealing. Leaky ducts can cost you 20 to 30 percent of your system’s output. In a larger Frisco home, that adds up fast. We inspect, repair, and seal ductwork throughout the area.

Why Frisco Homeowners Choose Adon Complete

Frisco has no shortage of HVAC companies competing for business. Here’s why our customers keep calling us back.

We know multi-zone and communicating systems. The job notes from our Frisco calls show what we actually work on here – damper adjustments, multi-system diagnostics, communicating Trane equipment, humidity management in two-story homes. This isn’t routine work, and we handle it well.

Jesse Villarreal has over 27 years of experience. He’s the owner and is directly involved in how the business operates. When something goes wrong, you’re dealing with a company where the owner’s reputation is on the line.

We’re a Trane Comfort Specialist and Mitsubishi-authorized dealer. Factory-trained on the brands most common in Frisco’s newer construction. Full manufacturer warranty on every system we install.

The Adon Care Club is $12 a month. Two tune-ups a year, priority scheduling, repair discounts, no diagnostic fees, and 24/7 emergency access. Straightforward and affordable.

Serving Frisco and Surrounding Collin County Communities

We serve all of Frisco, including The Fields, Phillips Creek Ranch, Viridian, Stonebriar, and the established neighborhoods along Preston Road and the Dallas North Tollway. We also serve the surrounding communities of Allen, McKinney, Anna, Melissa, and Sherman.

Schedule HVAC Service in FriscoCall (903) 482-4900

Frequently Asked Questions

Here are some common questions we get about our HVAC services in Frisco.

How much does AC repair cost in Frisco, TX?

Most AC repairs in Frisco run between $150 and $600 depending on the type of repair. Frisco’s newer homes often have multi-zone systems and higher-end equipment, which can affect parts costs. We provide a clear estimate before any work begins. Call (903) 482-4900 to schedule a diagnostic visit.

Do you service multi-zone systems in Frisco?

Yes. Multi-zone systems and communicating HVAC equipment are common in Frisco’s larger homes, and our technicians work on them regularly. We service all makes and models, including Trane, Lennox, Carrier, Daikin, Mitsubishi, and more.

Do you offer HVAC maintenance plans in Frisco?

Yes. Our Adon Care Club is $12 a month and includes two seasonal tune-ups, priority scheduling, repair discounts, no diagnostic fees, and 24/7 emergency response. Preventive maintenance is especially important for the multi-system setups common in Frisco’s larger homes.

Do you offer emergency HVAC service in Frisco?

Yes. We offer 24/7 emergency heating and air conditioning service throughout Frisco. When you call after hours, you reach a real person who can get a technician to your home fast.

What areas near Frisco do you serve?

We serve all of Frisco and the surrounding communities including Allen, McKinney, Anna, Melissa, and Sherman.

Ready to Get Your System Serviced?

Call Adon Complete Air Conditioning and Heating at (903) 482-4900 or schedule online for HVAC services in Frisco. We handle everything from routine maintenance to emergency repairs throughout Frisco and Collin County.

Schedule HVAC Service in FriscoCall (903) 482-4900

Recent Jobs and Reviews in Frisco, TX

Rated 5.0 out of 5 stars based on 7 customer reviews

Customers say: The overall sentiment across these reviews is overwhelmingly positive, reflecting strong customer satisfaction and appreciation for the service provided. Customers consistently praise the professionalism, knowledge, and efficiency of the technicians, highlighting their courteous demeanor and thorough explanations of work performed. A recurring theme is the company's responsiveness, with many reviewers expressing gratitude for quick arrival times, same-day or next-day service, and emergency availability during hot weather conditions. The honest, straightforward approach without upselling or gimmicks is frequently mentioned as a standout quality that builds trust. Customers appreciate the clear communication from both technicians and office staff, including timely updates on arrival times. The friendly and patient attitudes of service providers, even in stressful situations, earn particular commendation. Many reviewers indicate they would highly recommend the company and plan to use their services again, with several noting this is their preferred choice after multiple positive experiences. The tone is enthusiastic and grateful, with customers feeling valued and well-served, particularly during urgent situations involving AC failures in extreme heat. Overall, the reviews convey a strong sense of reliability, integrity, and customer-focused service that generates loyalty and satisfaction.

Frisco, TX at a glance

Adon Complete Air Conditioning and Heating has completed 10 jobs in Frisco, TX between September 2025 and November 2025.

The most recent job was on November 25, 2025.

Adon Complete Air Conditioning and Heating has completed 51 jobs in Frisco, TX in the last 12 months. The first job there was in March 2020.

Job Locations

Brayden W.
Brayden W.
Arrived on site for heating maintenance on carrier two system 2017-2016 furnaces. Homeowner stated all was well with regard to normal unit operation to his knowledge. Proceeded with scheduled heating maintenance. 1. Visually inspected condenser coil for debris/ dirty. 2. Inspected condenser fan motor. 3. Inspected condenser fan blades. 4. Inspected/ cleaned wiring connections. 5. Tested for gas leaks 6. Tested functionality and cleaned flame sensor 7. Tested functionality and cleaned pressure switches and ports 8. Inspected / replaced return filter. 9. Inspected return plenum for debris/ dirty. 10. Inspected evaporator coil. 11. Tested functionality and visually inspected surface igniter 12. Checked blower amp draw. 13. Measured temperature differential from supply to return. 20 degrees measured. Noticed large amount of noise coming from inducer motor on downstairs unit. Made slight adjustment to induce her housing, and the noise went away altogether. This leads me to believe that t
Frisco, TX 75035
Frisco, TX - Arrived on site for heating maintenance on carrier two system 2017-2016 furnaces. Homeowner stated all was well with regard to normal unit operation to his knowledge. Proceeded with scheduled heating maintenance.

 1. Visually inspected condenser coil for debris/ dirty.
2. Inspected condenser fan motor.
3. Inspected condenser fan blades.
4. Inspected/ cleaned wiring connections.
5. Tested for gas leaks
6. Tested functionality and cleaned flame sensor
7. Tested functionality and cleaned pressure switches and ports
8. Inspected / replaced return filter.
9. Inspected return plenum for debris/ dirty.
10. Inspected evaporator coil.
11. Tested functionality and visually inspected surface igniter
12. Checked blower amp draw.
13. Measured temperature differential from supply to return. 20 degrees measured.

Noticed large amount of noise coming from inducer motor on downstairs unit. Made slight adjustment to induce her housing, and the noise went away altogether. This leads me to believe that t
Frisco, TX - Arrived on site for heating maintenance on carrier two system 2017-2016 furnaces. Homeowner stated all was well with regard to normal unit operation to his knowledge. Proceeded with scheduled heating maintenance.

 1. Visually inspected condenser coil for debris/ dirty.
2. Inspected condenser fan motor.
3. Inspected condenser fan blades.
4. Inspected/ cleaned wiring connections.
5. Tested for gas leaks
6. Tested functionality and cleaned flame sensor
7. Tested functionality and cleaned pressure switches and ports
8. Inspected / replaced return filter.
9. Inspected return plenum for debris/ dirty.
10. Inspected evaporator coil.
11. Tested functionality and visually inspected surface igniter
12. Checked blower amp draw.
13. Measured temperature differential from supply to return. 20 degrees measured.

Noticed large amount of noise coming from inducer motor on downstairs unit. Made slight adjustment to induce her housing, and the noise went away altogether. This leads me to believe that t
Shelby S.
Shelby S.
Returned to install 4 surge protectors and an ecm blower motor. I needed a 4 leg belly strap to mount the motor. This strap was not a perfect match for the existing holes. I had to do a complete remount of the motor ensure it was centered and operational. I collected via check for the remaining amount.
Frisco, TX 75035
Frisco, TX - Returned to install 4 surge protectors and an ecm blower motor. I needed a 4 leg belly strap to mount the motor. This strap was not a perfect match for the existing holes. I had to do a complete remount of the motor ensure it was centered and operational. I collected via check for the remaining amount.
Frisco, TX - Returned to install 4 surge protectors and an ecm blower motor. I needed a 4 leg belly strap to mount the motor. This strap was not a perfect match for the existing holes. I had to do a complete remount of the motor ensure it was centered and operational. I collected via check for the remaining amount.
Jesse V.
Jesse V.
Arrived on site for 4 system heating maintenance. Homeowner stated all was well with normal unit operation to her knowledge. Discussed surge protection with the homeowner to protect the hvac equipment. Proceeded with maintenance as scheduled. 1. Visually inspected condenser coil for debris/ dirty. 2. Inspected condenser fan motor. 3. Inspected condenser fan blades. 4. Inspected/ cleaned wiring connections. 5. Tested for gas leaks 6. Tested functionality and cleaned flame sensor 7. Tested functionality and cleaned pressure switches and ports 8. Inspected / replaced return filter. 9. Inspected return plenum for debris/ dirty. 10. Inspected evaporator coil. 11. Tested functionality and visually inspected surface igniter 12. Checked blower amp draw. 13. Measured temperature differential from supply to return. 20 degrees measured. Upon testing the media room unit, it was found that the blower motor was not working. Further testing revealed that the motor was receiving signal from the con
Frisco, TX 75035
Frisco, TX - Arrived on site for 4 system heating maintenance. Homeowner stated all was well with normal unit operation to her knowledge. Discussed surge protection with the homeowner to protect the hvac equipment.  Proceeded with maintenance as scheduled. 
1. Visually inspected condenser coil for debris/ dirty.
2. Inspected condenser fan motor.
3. Inspected condenser fan blades.
4. Inspected/ cleaned wiring connections.
5. Tested for gas leaks
6. Tested functionality and cleaned flame sensor
7. Tested functionality and cleaned pressure switches and ports
8. Inspected / replaced return filter.
9. Inspected return plenum for debris/ dirty.
10. Inspected evaporator coil.
11. Tested functionality and visually inspected surface igniter
12. Checked blower amp draw.
13. Measured temperature differential from supply to return. 20 degrees measured.

Upon testing the media room unit, it was found that the blower motor was not working. Further testing revealed that the motor was receiving signal from the con
Frisco, TX - Arrived on site for 4 system heating maintenance. Homeowner stated all was well with normal unit operation to her knowledge. Discussed surge protection with the homeowner to protect the hvac equipment.  Proceeded with maintenance as scheduled. 
1. Visually inspected condenser coil for debris/ dirty.
2. Inspected condenser fan motor.
3. Inspected condenser fan blades.
4. Inspected/ cleaned wiring connections.
5. Tested for gas leaks
6. Tested functionality and cleaned flame sensor
7. Tested functionality and cleaned pressure switches and ports
8. Inspected / replaced return filter.
9. Inspected return plenum for debris/ dirty.
10. Inspected evaporator coil.
11. Tested functionality and visually inspected surface igniter
12. Checked blower amp draw.
13. Measured temperature differential from supply to return. 20 degrees measured.

Upon testing the media room unit, it was found that the blower motor was not working. Further testing revealed that the motor was receiving signal from the con
Shelby S.
Shelby S.
Upon arrival, I found that the outdoor unit had lost high voltage due to a tripped breaker. I began diagnosing by checking for issues that would cause the breaker to trip. I found that the compressor has become short to ground. I verified warranty on the equipment. It is coverage until 2028. The route to repair is either compressor replacement or system replacement. With a compressor replacement, it is necessary to put virgin (unused) refrigerant back into system and replace the refrigerant filter dryer. An estimate was generated for labor, refrigerant, and refrigerant filter dryer. Also, I observed that the drain has become clogged since last service. Both the upstairs and downstairs drains are tied together. Jacob and I have both offered compressor savers for both systems and customer has declined them on multiple occasions.
Frisco, TX 75036
Frisco, TX - Upon arrival, I found that the outdoor unit had lost high voltage due to a tripped breaker. I began diagnosing by checking for issues that would cause the breaker to trip. I found that the compressor has become short to ground. I verified warranty on the equipment. It is coverage until 2028. The route to repair is either compressor replacement or system replacement. With a compressor replacement, it is necessary to put virgin (unused) refrigerant back into system and replace the refrigerant filter dryer. An estimate was generated for labor, refrigerant, and refrigerant filter dryer. Also, I observed that the drain has become clogged since last service. Both the upstairs and downstairs drains are tied together. 

Jacob and I have both offered compressor savers for both systems and customer has declined them on multiple occasions.
Frisco, TX - Upon arrival, I found that the outdoor unit had lost high voltage due to a tripped breaker. I began diagnosing by checking for issues that would cause the breaker to trip. I found that the compressor has become short to ground. I verified warranty on the equipment. It is coverage until 2028. The route to repair is either compressor replacement or system replacement. With a compressor replacement, it is necessary to put virgin (unused) refrigerant back into system and replace the refrigerant filter dryer. An estimate was generated for labor, refrigerant, and refrigerant filter dryer. Also, I observed that the drain has become clogged since last service. Both the upstairs and downstairs drains are tied together. 

Jacob and I have both offered compressor savers for both systems and customer has declined them on multiple occasions.
Brayden W.
Brayden W.
performed heating maintenance. 1. Visually inspected condenser coil for debris/ dirty. 2. Inspected condenser fan motor. 3. Inspected condenser fan blades. 4. Inspected/ cleaned wiring connections. 5. Inspected flame sensor and igniter 6. Tested pressure switches and various safeties for functionality 7. Tested normal operation of burners 8. Inspected / replaced return filter. 9. Inspected return plenum for debris/ dirty. 10. Inspected evaporator coil. 11. Inspected blower motor/ blower wheel. 12. Checked inducer motor amp draw. 13. Measured temperature differential from supply to return. 20 degrees measured. 14. Inspected drain lines and treated to prevent blockages 15. Replaced downstairs filter but did not have another filter to replace the upstairs. Homeowner has ordered and will replace. Unit in good working order upon departure
Frisco, TX 75035
Frisco, TX - performed heating maintenance. 
1. Visually inspected condenser coil for debris/ dirty.
2. Inspected condenser fan motor.
3. Inspected condenser fan blades.
4. Inspected/ cleaned wiring connections.
5. Inspected flame sensor and igniter
6. Tested pressure switches and various safeties for functionality
7. Tested normal operation of burners 
8. Inspected / replaced return filter.
9. Inspected return plenum for debris/ dirty.
10. Inspected evaporator coil.
11. Inspected blower motor/ blower wheel.
12. Checked inducer motor amp draw.
13. Measured temperature differential from supply to return. 20 degrees measured.
14. Inspected drain lines and treated to prevent blockages 
15. Replaced downstairs filter but did not have another filter to replace the upstairs. Homeowner has ordered and will replace.

Unit in good working order upon departure
Frisco, TX - performed heating maintenance. 
1. Visually inspected condenser coil for debris/ dirty.
2. Inspected condenser fan motor.
3. Inspected condenser fan blades.
4. Inspected/ cleaned wiring connections.
5. Inspected flame sensor and igniter
6. Tested pressure switches and various safeties for functionality
7. Tested normal operation of burners 
8. Inspected / replaced return filter.
9. Inspected return plenum for debris/ dirty.
10. Inspected evaporator coil.
11. Inspected blower motor/ blower wheel.
12. Checked inducer motor amp draw.
13. Measured temperature differential from supply to return. 20 degrees measured.
14. Inspected drain lines and treated to prevent blockages 
15. Replaced downstairs filter but did not have another filter to replace the upstairs. Homeowner has ordered and will replace.

Unit in good working order upon departure
Shelby S.
Shelby S.
I performed a 2 system heating maintenance on 2018 heat pump systems. I checked amps, capacitors, filters, electrical, cleanliness, heat kits, and safeties. I found that both systems are in need of cleaning, the blower motor on the upstairs unit is missing the keeper screw causing it emit a scrapping noise and damaging the motor itself, both u/v sticks are burnt out, and both outdoor units need hard start kits. I produced options to address these issues. Home owner was not home at the time of service, and I emailed options over for review. I was informed about areas of the downstairs being uncomfortable due to over cooling. I inspected the zoning system. I noticed that the dampers were set to allow air to all areas to the house to relieve pressure inside of the system. I adjusted the dampers to stop allowing air to “bleed” into other areas of the home. I confirmed the system has a bypass, but doing this may cause an issue.
Frisco, TX 75036
Frisco, TX - I performed a 2 system heating maintenance on 2018 heat pump systems. I checked amps, capacitors, filters, electrical, cleanliness, heat kits, and safeties. I found that both systems are in need of cleaning, the blower motor on the upstairs unit is missing the keeper screw causing it emit a scrapping noise and damaging the motor itself, both u/v sticks are burnt out, and both outdoor units need hard start kits. I produced options to address these issues. Home owner was not home at the time of service, and I emailed options over for review. 
I was informed about areas of the downstairs being uncomfortable due to over cooling. I inspected the zoning system. I noticed that the dampers were set to allow air to all areas to the house to relieve pressure inside of the system. I adjusted the dampers to stop allowing air to “bleed” into other areas of the home. I confirmed the system has a bypass, but doing this may cause an issue.
Frisco, TX - I performed a 2 system heating maintenance on 2018 heat pump systems. I checked amps, capacitors, filters, electrical, cleanliness, heat kits, and safeties. I found that both systems are in need of cleaning, the blower motor on the upstairs unit is missing the keeper screw causing it emit a scrapping noise and damaging the motor itself, both u/v sticks are burnt out, and both outdoor units need hard start kits. I produced options to address these issues. Home owner was not home at the time of service, and I emailed options over for review. 
I was informed about areas of the downstairs being uncomfortable due to over cooling. I inspected the zoning system. I noticed that the dampers were set to allow air to all areas to the house to relieve pressure inside of the system. I adjusted the dampers to stop allowing air to “bleed” into other areas of the home. I confirmed the system has a bypass, but doing this may cause an issue.
Shelby S.
Shelby S.
Demand call for upstairs system not cooling properly and having iced over. Customer did thaw out the system and the ice was cleared by the time we got here. Found the filter to be dirty, customer stated it’s only been in there for a month. Turned the system on and checked pressures and found the system to be low. Performed a leak search on indoor coil and couldn’t find anything. The outside coil has leak coming from the high pressure switch stem. Customer was outside with us and was able to see the leak himself with the soap bubbles we used. Our install crew is scheduled to come out tomorrow at 9am to do the repair.
Frisco, TX 75035
Frisco, TX - Demand call for upstairs system not cooling properly and having iced over. Customer did thaw out the system and the ice was cleared by the time we got here. 
Found the filter to be dirty, customer stated it’s only been in there for a month. Turned the system on and checked pressures and found the system to be low. 
Performed a leak search on indoor coil and couldn’t find anything. The outside coil has leak coming from the high pressure switch stem. Customer was outside with us and was able to see the leak himself with the soap bubbles we used. 
Our install crew is scheduled to come out tomorrow at 9am to do the repair.
Brayden W.
Brayden W.
1. Visually inspected condenser coil for debris/ dirty. 2. Inspected condenser fan motor. 3. Inspected condenser fan blades. 4. Inspected/ cleaned wiring connections. 5. Tested compressor/ condenser fan motor capacitor. 6. Checked safety sensors and pressure switch 7. Checked condenser fan motor amp draw. 8. Inspected return filter 9. Inspected return plenum for debris 10. Measured temperature differential from supply to return. 20 degrees measured. 11. Inspected drain lines and treated to prevent blockages and treated 12. Tested and cleaned flame sensor. Service switch at furnace stopped working after cycling power. Unwired switch and all was working as intended. All is well unit regards to normal unit operation. Unit in good working order upon departure.
Frisco, TX 75035
Frisco, TX - 1. Visually inspected condenser coil for debris/ dirty.
2. Inspected condenser fan motor.
3. Inspected condenser fan blades.
4. Inspected/ cleaned wiring connections.
5. Tested compressor/ condenser fan motor capacitor.
6. Checked safety sensors and pressure switch
7. Checked condenser fan motor amp draw.
8. Inspected return filter
9. Inspected return plenum for debris
10. Measured temperature differential from supply to return. 20 degrees measured.
11. Inspected drain lines and treated to prevent blockages and treated
12. Tested and cleaned flame sensor.
Service switch at furnace stopped working after cycling power. Unwired switch and all was working as intended.
All is well unit regards to normal unit operation. Unit in good working order upon departure.
Frisco, TX - 1. Visually inspected condenser coil for debris/ dirty.
2. Inspected condenser fan motor.
3. Inspected condenser fan blades.
4. Inspected/ cleaned wiring connections.
5. Tested compressor/ condenser fan motor capacitor.
6. Checked safety sensors and pressure switch
7. Checked condenser fan motor amp draw.
8. Inspected return filter
9. Inspected return plenum for debris
10. Measured temperature differential from supply to return. 20 degrees measured.
11. Inspected drain lines and treated to prevent blockages and treated
12. Tested and cleaned flame sensor.
Service switch at furnace stopped working after cycling power. Unwired switch and all was working as intended.
All is well unit regards to normal unit operation. Unit in good working order upon departure.
Jacob P.
Jacob P.
***Trail for 30 days before collecting payment*** Returned to home to install wireless temperature sensor to the upstairs thermostat. I connected the sensor and gave it 100% temperature control for the zone. Paul asked if we could put the sensor in his son’s bedroom. This room has a half dome window without shade. Once we placed the sensor in this space we allowed it to adjust on its own and it reached the existing set point of 73º. The thermostat displays the temperature read by the wireless sensor and we discussed the importance of changing the batteries to ensure the upstairs space stays comfortable. The wireless sensor reached the 73º set point and shut off the unit. This is an immediate sign that the system is functioning and cooling properly and that the residual heat affecting the wall mounted thermostat should no longer be an issue. We will still give Paul 30 day trail before charging the card on file.
Frisco, TX 75035
Frisco, TX - ***Trail for 30 days before collecting payment***

Returned to home to install wireless temperature sensor to the upstairs thermostat. I connected the sensor and gave it 100% temperature control for the zone. Paul asked if we could put the sensor in his son’s bedroom. This room has a half dome window without shade. Once we placed the sensor in this space we allowed it to adjust on its own and it reached the existing set point of 73º. The thermostat displays the temperature read by the wireless sensor and we discussed the importance of changing the batteries to ensure the upstairs space stays comfortable.

The wireless sensor reached the 73º set point and shut off the unit. This is an immediate sign that the system is functioning and cooling properly and that the residual heat affecting the wall mounted thermostat should no longer be an issue. We will still give Paul 30 day trail before charging the card on file.
Frisco, TX - ***Trail for 30 days before collecting payment***

Returned to home to install wireless temperature sensor to the upstairs thermostat. I connected the sensor and gave it 100% temperature control for the zone. Paul asked if we could put the sensor in his son’s bedroom. This room has a half dome window without shade. Once we placed the sensor in this space we allowed it to adjust on its own and it reached the existing set point of 73º. The thermostat displays the temperature read by the wireless sensor and we discussed the importance of changing the batteries to ensure the upstairs space stays comfortable.

The wireless sensor reached the 73º set point and shut off the unit. This is an immediate sign that the system is functioning and cooling properly and that the residual heat affecting the wall mounted thermostat should no longer be an issue. We will still give Paul 30 day trail before charging the card on file.
Jacob P.
Jacob P.
Returned to our clients home to concerns that the upstairs unit was not keeping up and cooling properly. We ensured the unit was running on second stage and we then began measuring the refrigerant pressures. We contacted technical support and informed them that the drywall cavity directly behind the thermostat was reading 81/82º while the resort of the walls were measuring 74º. Due to the drastic temperature difference tech support recommended a wireless temperature sensor be connected somewhere else in the room. And that it be left and monitored for 30 days. We ensured the Freon pressured were correct and presented the option for the wireless sensor to Paul. He agreed to try it and we will order the part. Once allocated we will contact him to return and connect the sensor. We did also use silicone to seal off residual heat that has been altering the accuracy of the thermostat. This was not suggest by technical support but seemed to help reduce residual heat affecting the thermostat
Frisco, TX 75035
Frisco, TX - Returned to our clients home to concerns that the upstairs unit was not keeping up and cooling properly. We ensured the unit was running on second stage and we then began measuring the refrigerant pressures. We contacted technical support and informed them that the drywall cavity directly behind the thermostat was reading 81/82º while the resort of the walls were measuring 74º. Due to the drastic temperature difference tech support recommended a wireless temperature sensor be connected somewhere else in the room. And that it be left and monitored for 30 days. We ensured the Freon pressured were correct and presented the option for the wireless sensor to Paul. He agreed to try it and we will order the part. Once allocated we will contact him to return and connect the sensor.

We did also use silicone to seal off residual heat that has been altering the accuracy of the thermostat. This was not suggest by technical support but seemed to help reduce residual heat affecting the thermostat
Frisco, TX - Returned to our clients home to concerns that the upstairs unit was not keeping up and cooling properly. We ensured the unit was running on second stage and we then began measuring the refrigerant pressures. We contacted technical support and informed them that the drywall cavity directly behind the thermostat was reading 81/82º while the resort of the walls were measuring 74º. Due to the drastic temperature difference tech support recommended a wireless temperature sensor be connected somewhere else in the room. And that it be left and monitored for 30 days. We ensured the Freon pressured were correct and presented the option for the wireless sensor to Paul. He agreed to try it and we will order the part. Once allocated we will contact him to return and connect the sensor.

We did also use silicone to seal off residual heat that has been altering the accuracy of the thermostat. This was not suggest by technical support but seemed to help reduce residual heat affecting the thermostat